← Back to Tools
💨
Ventilation · Part F

Natural Ventilation Calculator

Calculate purge vent area, background ventilation and extract rates per UK Approved Document F.

Room Type

Room Dimensions (mm)

Results

Room Volume

Floor Area

ACH Estimate

changes/hr

Purge vent area
Background vent
Extract rate

Part F Requirements

Purge vent (habitable) 1/20 of floor area
Purge vent (wet room) 1/20 of floor area
Background (habitable) 8000 mm² ea
Background (wet room) 4000 mm² ea
Extract — Kitchen 60 l/s (or 30 adj)
Extract — Bathroom 15 l/s
Extract — WC 6 l/s
Extract — Utility 30 l/s

Trickle Vent Sizes

Small trickle vent 2500 mm²
Standard trickle vent 4000 mm²
Large trickle vent 8000 mm²
Slot vent (over-frame) 5000 mm²

ACH Estimate

Air changes per hour (ACH) is estimated from openable window area using ACH = (opening area × wind speed × 3600) / volume. Assumes 1 m/s average wind speed. Real ACH depends on wind, stack effect and building airtightness.